• Overall cladding to building poorly fitted and incorrectly fitted where terminated to the brickwork with no sill detail and varies from sat on brickwork to overhanging in places – because of this poor detail any water running down the cladding can possibly enter the building at multiple locations and needs to be investigated further.

• Down pipe drainage is poorly designed and runs through the cladding on a 90 degree angles causing debris to collect blocking the water flow putting pressure on the joints and over time cause leaks at joints – Clean down pipes / possible pipe re-route for better long term solution.

• Capping detail to top main roof poorly completed leaving exposed timber and degrading vapour barrier – this need another survey to work out a good solution to seal exposed area.

• Clean all debris from main roof area and would recommend ELD roof test to highlight future issues with the membrane.

• Replace damaged cladding and check fixings across building because in places fixing where loose and could call cause issues in adverse weather.

• Roof detail above smoke detector is really poor and need detailed inspection on build up and long term solution option.

Document date: 26-09-2020

Overview

Cladding abutment detail incorrect

Cladding abutment detail incorrect

Overview

Overview

Overview

Overview

Overview

Overview

Down pipe joint failure

Fixings loose on cladding detail

Overview

Overview

Overview

Down pipe joint leak

Down pipe joint leak

Down pipe joint leak

Cladding abutment joint incorrect

Cladding abutment joint incorrect

Overview

Overview

Down pipe detail poor design

Down pipe detail poor design

Down pipe detail poor design

Down pipe detail poor design

VCL exposed, roof cleaning required

VCL exposed, roof cleaning required

Overview

Overview

Overview

Overview

Capping detail sealant failure

Capping detail sealant failure

Capping detail sealant failure

Capping detail sealant failure

VCL exposed and incorrect capping detail profile

VCL exposed and incorrect capping detail profile

Debris on roof

Debris on roof

Debris on roof

Overview

Overview

Overview

Overview

Overview

Overview

Overview

Overview

Overview

Failed roof build up over smoke vent

Failed roof build up over smoke vent

Failed roof build up over smoke vent

Failed roof build up over smoke vent

Rain screen overview

Rain screen overview

Sealant failure

Previous leak location to below apartments

Overview

Overview

Overview

Overview

VCL exposed

Overview

Overview

Overview

Overview

Overview

Overview

Overview